A complete fuel shut off fuel train for use with gas turbine engines.
Continental Controls Corporation’s FT10 comes pre-assembled with 1 ½” valves, ensuring convenient installation. The FT10 is compatible with various fuels, including natural gas, propane, and more. The Fuel Train isolation valve provides shutdown on a gas turbine by rapidly halting gaseous fuel flow. The valve utilizes the supply pressure to move a spring-loaded piston. When the valve is energized, gas pressure drives the spring‐loaded piston open, admitting fuel to the turbine. When the current signal to the electrical solenoid is interrupted, the spring-loaded second‐stage piston changes state to vent off primary control pressure. The main spring then forces the primary piston to seal, stopping all flow.